NA2XRY (YJLV32) 0.6-1kV 3 Core Cable

NA2XRY (YJLV32) 0.6-1kV 3 Core Cable

APPLICATION These power cables are used for electricity supply in low voltage installation systems. They are well adapted to underground use in industrial appli
APPLICATION
These power cables are used for electricity supply in low voltage installation systems. They are well adapted to underground use in industrial applications with an additional mechanical protection. They are suitable for laying Indoor, tunnel, cable trench, shaft or buried laying, The cable can withstand mechanical external forces and a certain tensile force, it widely used in transformer stations, electric power plants and industrial plants.
CONSTRUCTION
● Conductor: Aluminum, class 1 or class 2, solid or stranded, circular or circular compacted conductors
● Insulation: Cross-linked polyethylene XLPE
● Filler: Non-hygroscopic material
● Binder: Non-hygroscopic material
● Inner sheath: Polyvinyl chloride PVC
● Armour: Steel wire
● Binder: Non-hygroscopic material
● Outer sheath: Polyvinyl chloride PVC
MAIN CHARACTERRISTICS
Good electrical and mechanical properties. Cross-linked polyethylene insulation allows greater power capacity under any operating condition, minimum dielectric losses, high insulation resistance. The PVC outer sheath allows an adequate resistance to oil and abrasion.
SPECIFICATION
IEC 60228 Conductors of Insulate Cables
IEC 60502-1 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from         1kV(Um=1.2kV) up to 30kV(Um=36kV) - Part 1: Cables for Rated Voltages of 1kV (Um=1.2kV) and       3kV(Um=3.6kV)
Parameter
IEC 60502-1
No. of Cores and Nominal Cross Section Min. Number of Wires Nominal Insulation Thickness Nominal Nominal Approx. Approx. Weight Max. D.C. Resistance of Conductor
Steel Wire Diameter Sheath Thickness Overall Diameter at 20℃
No. × mm² No. mm mm mm mm kg/km Ω/km
2×2.5 1 0.7 0.8 1.8 14.1 314 12.1
2×4 1 0.7 0.8 1.8 15.1 357 7.41
2×6 1 0.7 0.8 1.8 16.1 406 4.61
2×10 6 0.7 1.25 1.8 19.5 619 3.08
2×16 6 0.7 1.25 1.8 21.1 743 1.91
2×25 6 0.9 1.6 1.8 25 1078 1.2
2×35 6 0.9 1.6 1.8 27 1243 0.868
2×50 6 1 1.6 1.8 30 1459 0.641
2×70 12 1.1 1.6 2 33.8 1796 0.443
2×95 15 1.1 2 2.1 39.1 2495 0.32
2×120 15 1.2 2 2.2 42.5 2836 0.253
2×150 15 1.4 2 2.3 46.5 3330 0.206
2×185 30 1.6 2.5 2.5 52.3 4386 0.164
2×240 30 1.7 2.5 2.7 57.7 5192 0.125
2×300 30 1.8 2.5 2.8 63.1 6049 0.1
2×400 53 2 2.5 3.1 70.1 7194 0.0778
3×2.5 1 0.7 0.8 1.8 14.6 340 12.1
3×4 1 0.7 0.8 1.8 15.6 388 7.41
3×6 1 0.7 0.8 1.8 16.7 448 4.61
3×10 6 0.7 1.25 1.8 20.4 682 3.08
3×16 6 0.7 1.25 1.8 22.1 835 1.91
3×25 6 0.9 1.6 1.8 26.2 1221 1.2
3X35 6 0.9 1.6 1.8 28.4 1414 0.868
3×50 6 1 1.6 1.9 31.8 1681 0.641
3×70 12 1.1 2 2 37.2 2389 0.443
3×95 15 1.1 2 2.2 41.5 2895 0.32
 
No. of Cores and Nominal Cross Section Min. Number of Wires Nominal Insulation Thickness Nominal Nominal Approx. Approx. Weight Max. D.C. Resistance of Conductor
Steel Wire Diameter Sheath Thickness Overall Diameter at 20℃
No. × mm² No. mm mm mm mm kg/km Ω/km
3×120 15 1.2 2 2.3 45.2 3336 0.253
3×150 15 1.4 2.5 2.5 51.1 4415 0.206
3×185 30 1.6 2.5 2.6 55.6 5113 0.164
3×240 30 1.7 2.5 2.8 61.8 6188 0.125
3×300 30 1.8 2.5 3 67.4 7206 0.1
3×400 53 2 2.5 3.2 74.7 8623 0.0778
4×2.5 1 0.7 0.8 1.8 15.4 377 12.1
4×4 1 0.7 0.8 1.8 16.6 436 7.41
4×6 1 0.7 1.25 1.8 18.7 631 4.61
4×10 6 0.7 1.25 1.8 21.8 779 3.08
4×16 6 0.7 1.6 1.8 24.4 1076 1.91
4×25 6 0.9 1.6 1.8 28.3 1404 1.2
4×35 6 0.9 1.6 1.9 30.9 1645 0.868
4×50 6 1 1.6 2 34.7 1977 0.641
4×70 12 1.1 2 2.2 40.7 2829 0.443
4×95 15 1.1 2 2.3 45.3 3434 0.32
4×120 15 1.2 2.5 2.5 51 4442 0.253
4×150 15 1.4 2.5 2.6 55.8 5198 0.206
4×185 30 1.6 2.5 2.8 61.4 6194 0.164
4×240 30 1.7 2.5 3 67.9 7424 0.125
4×300 30 1.8 2.5 3.2 74.1 8695 0.1
4×400 53 2 3.15 3.5 84.1 11526 0.0778
5×2.5 1 0.7 0.8 1.8 16.3 419 12.1
5×4 1 0.7 1.25 1.8 18.5 606 7.41
5×6 1 0.7 1.25 1.8 19.9 704 4.61
5×10 6 0.7 1.25 1.8 23.3 870 3.08
5×16 6 0.7 1.6 1.8 26.1 1227 1.91
5×25 6 0.9 1.6 1.8 30.5 1597 1.2
5×35 6 0.9 1.6 1.9 33.4 1890 0.868
5×50 6 1 2 2.1 39.3 2609 0.641
 
No. of Cores and Nominal Cross Section Min. Number of Wires Nominal Insulation Thickness Nominal Nominal Approx. Approx. Weight Max. D.C. Resistance of Conductor
Steel Wire Diameter Sheath Thickness Overall Diameter at 20℃
No. × mm² No. mm mm mm mm kg/km Ω/km
5×70 12 1.1 2 2.3 44.3 3271 0.443
5×95 15 1.1 2.5 2.5 51 4494 0.32
5×120 15 1.2 2.5 2.6 55.5 5148 0.253
5×150 15 1.4 2.5 2.8 61.4 6181 0.206
5×185 30 1.6 2.5 3 67.2 7236 0.164
5×240 30 1.7 2.5 3.2 74.4 8761 0.125
5×300 30 1.8 3.15 3.4 82.9 11266 0.1
5×400 53 2 3.15 3.8 92.4 13590 0.0778
3×4+1×2.5 1/1 0.7/0.7 0.8 1.8 16.3 422 7.41/12.1
3×6+1×4 1/1 0.7/0.7 1.25 1.8 18.4 608 4.61/7.41
3×10+1×6 6/15 0.7/0.7 1.25 1.8 21 736 3.08/4.61
3×16+1×10 6/6 0.7/0.7 1.25 1.8 23.2 905 1.91/3.08
3×25+1×16 6/6 0.9/0.7 1.6 1.8 27.3 1321 1.20/1.91
3×35+1×16 6/6 0.9/0.7 1.6 1.8 29.1 1489 0.868/1.91
3×50+1×25 6/6 1.0/0.9 1.6 1.9 33 1831 0.641/1.20
3×70+1×35 12/6 1.1/0.9 2 2.1 38.6 2584 0.443/0.868
3×95+1×50 6/15 1.1/1.0 2 2.2 43 3114 0.320/0.641
3×120+1×70 12/15 1.2/1.1 2 2.4 47.3 3683 0.253/0.443
3×150+1×70 12/15 1.4/1.1 2.5 2.5 52.4 4719 0.206/0.443
3×185+1×95 30/15 1.6/1.1 2.5 2.7 57.5 5527 0.164/0.320
3×240+1×120 30/15 1.7/1.2 2.5 2.9 63.8 6672 0.125/0.253
3×300+1×150 30/15 1.8/1.4 2.5 3 69.5 7800 0.100/0.206
3×400+1×185 53/30 2.0/1.6 3.15 3.3 78.8 10313 0.0778/0.164
3×4+2×2.5 1/1 0.7/0.7 1.25 1.8 18 577 7.41/12.1
3×6+2×4 1/1 0.7/0.7 1.25 1.8 19.3 660 4.61/7.41
3×10+2×6 6/15 0.7/0.7 1.25 1.8 21.9 807 3.08/4.61
3×16+2×10 6/6 0.7/0.7 1.6 1.8 25.3 1138 1.91/3.08
3×25+2×16 6/6 0.9/0.7 1.6 1.8 28.7 1450 1.20/1.91
3×35+2×16 6/6 0.9/0.7 1.6 1.8 30.4 1614 0.868/1.91
3×50+2×25 6/6 1.0/0.9 2 2 36.4 2285 0.641/1.20
 
No. of Cores and Nominal Cross Section Min. Number of Wires Nominal Insulation Thickness Nominal Nominal Approx. Approx. Weight Max. D.C. Resistance of Conductor
Steel Wire Diameter Sheath Thickness Overall Diameter at 20℃
No. × mm² No. mm mm mm mm kg/km Ω/km
3×70+2×35 12/6 1.1/0.9 2 2.1 40.4 2814 0.443/0.868
3×95+2×50 6/15 1.1/1.0 2 2.3 45.4 3436 0.320/0.641
3×120+2×70 12/15 1.2/1.1 2.5 2.5 51.6 4566 0.253/0.443
3×150+2×70 12/15 1.4/1.1 2.5 2.6 54.9 5099 0.206/0.443
3×185+2×95 30/15 1.6/1.1 2.5 2.8 60.9 6138 0.164/0.320
3×240+2×120 30/15 1.7/1.2 2.5 3 67 7316 0.125/0.253
3×300+2×150 30/15 1.8/1.4 2.5 3.2 73.4 8591 0.100/0.206
3×400+2×185 53/30 2.0/1.6 3.15 3.5 83 11345 0.0778/0.164
4×4+1×2.5 1/1 0.7/0.7 1.25 1.8 18.2 587 7.41/12.1
4×6+1×4 1/1 0.7/0.7 1.25 1.8 19.6 682 4.61/7.41
4×10+1×6 6/15 0.7/0.7 1.25 1.8 22.6 838 3.08/4.61
4×16+1×10 6/6 0.7/0.7 1.6 1.8 25.7 1182 1.91/3.08
4×25+1×16 6/6 0.9/0.7 1.6 1.8 29.6 1515 1.20/1.91
4×35+1×16 6/6 0.9/0.7 1.6 1.9 32 1750 0.868/1.91
4×50+1×25 6/6 1.0/0.9 2 2.1 38 2485 0.641/1.20
4×70+1×35 12/6 1.1/0.9 2 2.2 42.4 3054 0.443/0.868
4×95+1×50 6/15 1.1/1.0 2 2.4 47.5 3726 0.320/0.641
4×120+1×70 12/15 1.2/1.1 2.5 2.5 53.4 4843 0.253/0.443
4×150+1×70 12/15 1.4/1.1 2.5 2.7 57.9 5608 0.206/0.443
4×185+1×95 30/15 1.6/1.1 2.5 2.9 64 6702 0.164/0.320
4×240+1×120 30/15 1.7/1.2 2.5 3.1 70.7 8012 0.125/0.253
4×300+1×150 30/15 1.8/1.4 3.15 3.3 79 10410 0.100/0.206
4×400+1×185 53/30 2.0/1.6 3.15 3.6 87.6 12438 0.0778/0.164

Contact Us, Now.
24-hour service hotline
Contact online customer service
Add: Technology Building, Tongbai Road, Zhongyuan District, Zhengzhou, Henan, China.
Related products
Turnnion Type Suspension Clamp
Turnnion Type Suspension Clamp
Preformed Distribution Side Tie for Insulators
Preformed Distribution Side Tie for Insulators
Anchor Dead End Clamp
PAM-06/PAM-07/PAM-08/PAM-09 Anchor Dead End Clamp
11KV distribution line lightning surge arrester
11KV distribution line lightning surge arrester