Application
Aerial Insulated Cables with voltages of 10kV.The products primarily used for the distribution of electrical energy under normal conditions of overhead (aerial) installations.The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer etc.
Description
The conductors are stranded,circular compressed aluminum, aluminum-alloy, copper. The conductor screen is the extruded Semi-conducting conductor shield in Black. And the outer Insulation is mainly thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE) in Black with Weather or UV resistant. This standard covers both thermoplastic and cross linked polyethylene constructions, rated for 75°C or 90°C normal service temperature.
Specifications
• GB/T 14049 (Equal to IEC 60502-2) Aerial Insulated Cables For Rated Voltage of 10kV
Parameter
IEC 60502-2
10kV Aerial Insulated Cables
10kV Aerial Insulated Cables
IEC 60502-2
22.9kV ACSR/AW-OC Aerial Insulated Cables
Aerial Insulated Cables with voltages of 10kV.The products primarily used for the distribution of electrical energy under normal conditions of overhead (aerial) installations.The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer etc.
Description
The conductors are stranded,circular compressed aluminum, aluminum-alloy, copper. The conductor screen is the extruded Semi-conducting conductor shield in Black. And the outer Insulation is mainly thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE) in Black with Weather or UV resistant. This standard covers both thermoplastic and cross linked polyethylene constructions, rated for 75°C or 90°C normal service temperature.
Specifications
• GB/T 14049 (Equal to IEC 60502-2) Aerial Insulated Cables For Rated Voltage of 10kV
Type | No. of Cores | Nominal size |
mm2 | ||
CU/XLPE,AAC/XLPE,AAAC/XLPE | 1 | 10 ~ 400 |
3 | 25 ~ 400 | |
3+k(A) or 3+k(B) | 25 ~ 400 ; k:25~120 | |
CU/PE,AAC/PE,AAAC/PE,CU/XLPE,AAC/XLPE,AAAC/XLPE | 1 | 10 ~ 400 |
AAC/XLPE,AAAC/XLPE | 3 | 25 ~ 400 |
3+k(A) or 3+k(B) | 25 ~ 400 ; k:25~120 |
Parameter
IEC 60502-2
10kV Aerial Insulated Cables
Nominal Size | Min. No. | Approx. Diameter of Conductor | Min. | Nominal Thickness of Insulation | Nominal Thickness of Insulation Screen | Max. DC Resistance at 20 0C | Min. Breaking Load | ||
of Wires | Thickness of Conductor screen | ||||||||
(Approx.) | Reduced | Nominal | Hard Copper | Soft Copper | Hard Copper | ||||
mm2 | No. | mm | mm | mm | mm | mm | Ω/km | Ω/km | N |
10 | 6 | 3.8 | 0.5 | - | 3.4 | - | - | 1.83 | - |
16 | 6 | 4.8 | 0.5 | - | 3.4 | - | - | 1.15 | - |
25 | 6 | 6 | 0.5 | 2.5 | 3.4 | 1 | 0.749 | 0.727 | 8465 |
35 | 6 | 7 | 0.5 | 2.5 | 3.4 | 1 | 0.54 | 0.524 | 11731 |
50 | 6 | 8.3 | 0.5 | 2.5 | 3.4 | 1 | 0.399 | 0.387 | 16052 |
70 | 12 | 10 | 0.5 | 2.5 | 3.4 | 1 | 0.276 | 0.268 | 23461 |
95 | 15 | 11.6 | 0.6 | 2.5 | 3.4 | 1 | 0.199 | 0.193 | 31759 |
120 | 18 | 13 | 0.6 | 2.5 | 3.4 | 1 | 0.158 | 0.153 | 39911 |
150 | 18 | 14.6 | 0.6 | 2.5 | 3.4 | 1 | 0.128 | - | 49505 |
185 | 30 | 16.2 | 0.6 | 2.5 | 3.4 | 1 | 0.1021 | - | 61846 |
240 | 34 | 18.4 | 0.6 | 2.5 | 3.4 | 1 | 0.0777 | - | 79823 |
300 | 34 | 20.6 | 0.6 | 2.5 | 3.4 | 1 | 0.0619 | - | 99788 |
400 | 53 | 23.8 | 0.6 | 2.5 | 3.4 | 1 | 0.0484 | - | 133040 |
Nominal Size | Min. No. | Approx. Diameter of Conductor | Min. | Nominal Thickness of Insulation | Nominal Thickness of Insulation Screen | Max. DC Resistance at 20 0C | Min. Breaking Load | |||
of Wires | Thickness of Conductor Screen | |||||||||
(Approx.) | Reduced | Nominal | AAC | AAAC | AAC | AAAC | ||||
mm2 | No. | mm | mm | mm | mm | mm | Ω/km | Ω/km | N | N |
10 | 6 | 3.8 | 0.5 | - | 3.4 | - | 3.08 | 3.574 | - | - |
16 | 6 | 4.8 | 0.5 | - | 3.4 | - | 1.91 | 2.217 | - | - |
25 | 6 | 6 | 0.5 | 2.5 | 3.4 | 1 | 1.2 | 1.393 | 3762 | 6284 |
35 | 6 | 7 | 0.5 | 2.5 | 3.4 | 1 | 0.868 | 1.007 | 5177 | 8800 |
50 | 6 | 8.3 | 0.5 | 2.5 | 3.4 | 1 | 0.641 | 0.744 | 7011 | 12569 |
70 | 12 | 10 | 0.5 | 2.5 | 3.4 | 1 | 0.443 | 0.514 | 10354 | 17596 |
95 | 15 | 11.6 | 0.6 | 2.5 | 3.4 | 1 | 0.32 | 0.371 | 13727 | 23880 |
120 | 18 | 13 | 0.6 | 2.5 | 3.4 | 1 | 0.253 | 0.294 | 17339 | 30164 |
150 | 18 | 14.6 | 0.6 | 2.5 | 3.4 | 1 | 0.206 | 0.239 | 21033 | 37706 |
185 | 30 | 16.2 | 0.6 | 2.5 | 3.4 | 1 | 0.164 | 0.19 | 26732 | 46503 |
240 | 34 | 18.4 | 0.6 | 2.5 | 3.4 | 1 | 0.125 | 0.145 | 34679 | 60329 |
300 | 34 | 20.6 | 0.6 | 2.5 | 3.4 | 1 | 0.1 | 0.116 | 43349 | 75411 |
400 | 53 | 23.8 | 0.6 | 2.5 | 3.4 | 1 | 0.0778 | 0.0904 | 55707 | 100548 |
22.9kV ACSR/AW-OC Aerial Insulated Cables
Size | No. and Dia. | Conductor Diameter | InsulatioThickness | Cable Diameter | Rated | Weight | |
(mm2) | of Wires | Strength | |||||
AL | St | ||||||
No. | No. /mm | mm | mm | mm | kgf | kg/km | |
22.9 kV ACSR/AW-OC/XLPE | |||||||
32 | 6/SB | 1/2.6 | 7.2 | 3 | 13.2 | 1090 | 210 |
58 | 6/SB | 1/3.5 | 9.7 | 3 | 15.7 | 1900 | 330 |
95 | 6/SB | 1/3.5 | 12 | 3.5 | 19 | 2360 | 530 |
160 | 18/SB | 1/3.2 | 15.4 | 4 | 23.4 | 3080 | 730 |
240 | 18/SB | 1/4.0 | 18.9 | 4 | 27 | 4500 | 1040 |