PVC Covered Conductor (BS 6485)

PVC Covered Conductor (BS 6485)

Application Two types of PVC-covered conductors for Overhead power lines.Type 8 is intended for use only where the operating voltage of the power lines does not
Application
Two types of PVC-covered conductors for Overhead power lines.Type 8 is intended for use only where the operating voltage of the power lines does not exceed 650 V r.m.s.between any two conductors or 250 V r.m.s. between any conductor and earth. Type 16 is intended for use only where the operating voltage of the power line exceeds 650 V r.m.s between any two conductors or 250 V r.m.s. between any conductor and earth, but does not normally exceed 11 kV r.m.s. between conductors or 6.6 kV r.m.s. between any conductor and earth.
Construction
The conductors are stranded, circular compressed or uncompressed aluminum, copper, aluminum-alloy, ACSR etc., concentrically stranded and covered for PVC in black (type 8) and green(type 16).
Specifications
• BS 6485 PVC-Covered Conductors For Overhead Power Lines
• BS EN 50182 Conductors For overhead lines — Round Wire Concentric Lay Stranded Conductors
• BS 215-1  Aluminum Conductors and  Aluminum Conductors,Steel-Reinforced —For Overhead Power Transmission Part 1:  Aluminum Stranded Conductors
• BS 215-2  Aluminum Conductors and  Aluminum Conductors,Steel-Reinforced —For Overhead Power Transmission Part 2:  Aluminum Conductors, Steel-Reinforced
• BS 3242  Aluminum Alloy Stranded Conductors For Overhead Power Transmission
• BS 7884 Copper and Copper-Cadmium Stranded Conductors For Overhead Electric Traction and Power Transmission Systems
Parameter
BS 6485,BS 215-1 PVC-Covered Conductors For Overhead Power Lines
Code Word Nominal cross-sectional area Stranding and Wire Diameter Approximate Overall Diameter of Bare Conductor Maximum Resistance per kilometre at 20 °C Approximate Breaking Load Approximate Overall Diameter of Covered Conductor Approximate Mass per kilometre of Covered Conductor
Type 8 Type 8
mm² mm mm  Ω kN mm kg/km
AAC/PVC
Midge 22 7/2.06 6.18 1.227 3.99 8.2 100
Aphis 25 3/3.35 7.2 1.081 4.11 9.2 133
Gnat 25 7/2.21 6.63 1.066 4.59 8.8 118
Weevil 30 3/3.66 7.9 0.9082 4.86 10.1 158
Mosquito 35 7/2.59 7.77 0.7762 6.03 10 156
Ladybird 40 7/2.79 8.37 0.6689 6.87 10.6 177
Ant 50 7/3.10 9.3 0.5419 8.28 11.7 200
Fly 60 7/3.40 10.2 0.4505 9.9 12.4 249
Bluebottle 70 7/3.66 11 0.3881 11.34 13.2 285
Earwing 75 7/3.78 11.3 0.3644 11.94 13.6 302
Grasshopper 80 7/3.91 11.7 0.3406 12.78 13.9 319
Clegg 90 7/4.17 12.5 0.2994 14.53 14.7 359
Wasp 100 7/4.39 13.17 0.2702 16 16 360
Beetle 100 19/2.67 13.4 0.2704 17.42 15.6 387
Bee 125 7/4.90 14.7 0.2169 19.94 16.9 482
Cricket 150 7/5.36 16.1 0.1813 23.85 18.3 567
Hornet 150 19/3.25 16.3 0.1825 27.7 18.5 538
Caterpillar 175 19/3.53 17.7 0.1547 28.63 19.9 646
Chafer 200 19/3.78 18.9 0.1349 32.4 21.7 690
Spider 225 19/3.99 20 0.1211 36.01 22.2 809
Cockroach 250 19/4.22 21.1 0.1083 40.4 23.3 900
Butterfly 300 19/4.65 23.3 0.08916 48.7 25.5 1082
Moth 350 19/5.00 25 0.07711 56.37 27.2 1241
Drone 350 37/3.58 25.1 0.07741 57.45 27.3 1222
Locust 400 19/5.36 26.8 0.0671 64.73 29 1416
Centipede 400 37/3.78 26.5 0.06944 63.1 28.7 1353
Maybug 450 37/4.09 28.6 0.05931 74.01 30.8 1573
Scorpion 500 37/4.27 29.9 0.05441 79.98 32.1 1706
Cicada 600 37/4.65 32.6 0.04588 94.95 34.8 2010
Tarantula 750 37/5.23 36.6 0.03627 120.1 38.8 2519
 
BS 6485,BS 7884
Nominal cross-sectional area Stranding and Wire Diameter Approximate Overall Diameter of Bare Conductor Maximum Resistance per kilometre at  20 °C Approximate Breaking Load Approximate Overall Diameter of Covered Conductor Approximate Mass per kilometre of Covered Conductor
Type 8 Type 16 Type 8 Type 16
mm² mm mm  Ω kN mm mm kg kg
CU/PVC
14 7/1.60 4.8 1.303 5.744 6.8 8.4 160 190
16 3/2.65 5.7 1.106 6.59 7.7 9.3 180 220
32 3/3.75 8.06 0.552 12.71 10.5 12.1 350 390
35 7/2.50 7.5 0.5337 14.097 9.9 11.5 360 400
70 7/3.55 10.65 0.2646 26.88 13.5 14.7 690 750
100 7/4.30 12.9 0.181 37.64 15.7 16.9 990 1060
 
Nominal cross-sectional area Stranding and Wire Diameter Approximate Overall Diameter of Bare Conductor Maximum Resistance per kilometre at 20 °C Approximate Breaking Load Approximate Overall Diameter of Covered Conductor Approximate Mass per kilometre of Covered Conductor
Type 16 Type 16
mm² mm mm Ω kN mm kg
COPPER-ALLOY / PVC
12 3/2.30 4.95 1.78 7.2 8.2 170
22 7/2.00 6 1.011 12.94 9.6 270
38 7/2.60 7.8 0.5983 21.69 11.8 430
75 7/3.70 11.1 0.2954 40.23 15.1 810
125 19/2.90 14.5 0.1784 68.75 18.5 1310
150 19/3.20 16 0.1465 82.16 20 1570
 
BS 6485,BS 215-2
Nominal cross-sectional area Stranding and Wire Diameter Approximate Overall Diameter of Bare Conductor Maximum Resistance per kilometre at 20 °C Approximate Breaking Load Approximate Overall Diameter of Covered Conductor Approximate Mass per kilometre of Covered Conductor
Aluminum Steel
Type 8 Type 16
mm² No./mm No./mm mm Ω kN mm kg
ACSR / PVC
25 6/2.36 1/2.36 7.08 1.093 9.61 10.7 190
50 6/3.35 1/3.35 10.05 0.5426 18.35 14.1 330
100 6/4.72 7/1.57 14.15 0.2733 32.7 18.2 550
150 30/2.59 7/2.59 18.13 0.1828 69.2 22.2 920
150 18/3.35 1/3.35 16.75 0.1815 35.7 20.8 680
175 30/2.79 7/2.79 19.53 0.1576 79.8 23.6 1050
175 18/3.61 1/3.61 18.05 0.1563 41.1 22.1 780
200 30/3.00 7/3.00 21 0.1363 92.25 25 1190
200 18/3.86 1/3.86 19.3 0.1367 46.55 23.3 870
 
BS 6485,BS 3242
Nominal cross-sectional area Stranding and Wire Diameter Approximate Overall Diameter of Bare Conductor Maximum Resistance per kilometre at 20 °C Approximate Breaking Load Approximate Overall Diameter of Covered Conductor Approximate Mass per kilometre of Covered Conductor
Type 16 Type 16
mm² mm mm Ω kN mm kg
AAAC / PVC
25 7/2.34 7.02 1.094 8.44 10.6 170
50 7/3.30 9.9 0.5498 16.8 13.9 280
100 7/4.65 13.95 0.2769 33.3 18 470
150 19/3.48 17.4 0.183 50.65 21.4 680
200 19/3.76 18.8 0.1568 59.1 22.8 780

Contact Us, Now.
24-hour service hotline
Contact online customer service
Add: Technology Building, Tongbai Road, Zhongyuan District, Zhengzhou, Henan, China.
Related products
Turnnion Type Suspension Clamp
Turnnion Type Suspension Clamp
Porcelain Guy Strain Insulator Tension Insulator
Porcelain Guy Strain Insulator Tension Insulator
Clevis
Clevis(Type Z, PS)
ADSS/OPGW Optical Cable Suspension Clamp Assembly
ADSS/OPGW Optical Cable Suspension Clamp Assembly